The ZN63A(VS1-12) Series Indoor Vacuum Circuit Breaker is a type of high-voltage AC indoor vacuum circuit breaker primarily designed for use in power systems with a rated voltage of up to 12KV and a three-phase AC 50Hz. This breaker is engineered to be compatible with KYN28A-12 high-altitude switchgear and is particularly suitable for use in high-altitude areas up to 3000 meters above sea level.

Product Description

Product Overview:

The ZN63A (VS1-12) series indoor high voltage vacuum circuit breaker is designed for use in 12kV, three-phase, 50Hz electrical systems. Developed by integrating advanced technology from Switzerland’s ABB company with national research and development capabilities, this circuit breaker provides reliable and safe interruption of electrical currents. It is ideal for various industrial, commercial, and utility applications.

Structural Features:

  1. Integrated Design:
    • The structure integrates the breaker body with the operating mechanism, ensuring a compact and efficient design.
  2. Composite Insulating Material:
    • Utilizes composite insulating material that is non-polluting, non-explosive, and offers a high insulation level, enhancing safety and reliability.
  3. Spring Charging Mechanism:
    • Features a spring charging operating mechanism that can be operated by an AC motor or manually by hand, providing flexibility in operation.
  4. High-Quality Construction:
    • Developed using advanced technology and robust materials, ensuring long-term durability and reliable performance.

Installation Method:

  1. Preparation:
    • Verify the circuit breaker specifications to ensure compatibility with the existing electrical system.
    • Prepare the installation area by cleaning and ensuring it is dry and free from dust and other contaminants.
  2. Mounting:
    • Securely mount the vacuum circuit breaker on a stable and rigid surface within the indoor electrical distribution panel or switchgear unit using the provided mounting brackets and hardware.
  3. Wiring Connections:
    • Connect the incoming and outgoing cables to the designated terminals, ensuring tight and secure connections. Follow the wiring diagram provided with the circuit breaker for correct electrical connections.
  4. Grounding:
    • Ensure proper grounding of the circuit breaker to prevent electrical hazards. Connect the grounding terminal to the panel or switchgear’s grounding busbar.
  5. Testing:
    • After installation, perform insulation resistance and continuity tests to ensure proper installation and functionality. Verify the operation of the circuit breaker by manually and motor-operating it several times.

Applicable Environmental Conditions:

  1. Temperature Range:
    • Operating temperature: -10°C to +40°C
    • Storage temperature: -30°C
  2. Altitude:
    • Suitable for altitudes up to 1000 meters.
  3. Humidity:
    • Daily average relative humidity: ≤95%
    • Monthly average relative humidity: ≤90%
  4. Water Vapor Pressure:
    • Daily average: ≤2.2×10³MPa
    • Monthly average: ≤1.8×10³MPa
  5. Seismic Resistance:
    • Capable of withstanding earthquakes with a grade less than Degree 8.
  6. Air Quality:
    • The ambient air should not be significantly polluted by dust, smoke, corrosive or flammable gases, vapors, or salt.

 

Specifications

Technical Parameters:

Item Unit Parameter
Rated voltage kV 12
Rated frequency Hz 50
Rated current A 630-1250 1250-1600
Rated short-circuit breaking current kA 20 25 31.5
Rated short-circuit making current kA 50 63 80
Rated peak withstand current kA 50 63 80
4s rated short-circuit withstand current kA 20 25 31.5
Rated insulation level Power frequency withstand voltage (before and after rated breaking) kV 42(phase to phase,to earth)/48(fracture)effective value

75(phase to phase,to earth)/85(fracture)peak

Lightning impulse withstand voltage (before and after rated breaking)
Rated operating sequence time On-0.3s-off on-180s-off on
Mechanical life time 20000
Rated short-circuit current breaking times V 50
Rated closing voltage of operating mechanism (DC) V AC/DC 110、220
Rated opening voltage of operating mechanism (DC) mm AC/DC 110、220
Clearance between open contacts mm 9±1
Overtravel (contact spring compression length) ms 3.5±0.5
Three-phase split, closing bounce time ms ≤2
Contact closing bounce time m/s ≤2

Product Advantages

  • Product structure and features:
  • 1 Vacuum arc extinguishing chamber
    The circuit breaker is equipped with an intermediate sealing type ceramic or glass vacuum arc extinguishing chamber, and adopts copper-chromium contact material and cup-shaped longitudinal magnetic field contact structure. The contact has small electrical wear rate, long electrical life, high voltage resistance level of the contact, stable dielectric insulation strength, fast recovery speed after arc, intercepting horizontal bottom, and strong opening ability
  • 2 Overall Structure
    The overall structure of the circuit breaker adopts the form of operating mechanism and arc extinguishing chamber before and after arrangement, the main circuit part is three-phase floor structure, the vacuum arc extinguishing chamber is longitudinally installed in a tubular insulation cylinder, the insulation cylinder is made of epoxy resin by APG process, so it is particularly resistant to creepage. This structure design greatly reduces the accumulation of dust on the surface of the interrupter, not only can prevent the vacuum interrupter from being damaged by external factors, but also can ensure that the voltage effect can show a high resistance state even in wet and hot and serious dirty environment
  • 3 Operate the mechanism
    The operating mechanism is a flat arranged spring energy storage operating mechanism with manual energy storage and electric energy storage functions. The operating mechanism is placed in the mechanism box in front of the arc extinguishing chamber, and the mechanism box of the circuit breaker is used as the framework of the operating mechanism.
  • 4 The circuit breaker has the advantages of long life, simple maintenance, no pollution, no explosion danger, low noise, and is suitable for harsh working conditions such as frequent operation. The circuit breaker can be loaded into the hand-operated switchgear. Can also be used for fixed switchgear.
ZN63A(VS1-12) Series Indoor Vacuum Circuit Breaker

Application Places

ZN63(VS1-12C)-12C indoor AC vacuum circuit breaker is suitable for rated voltage zone 12 kV, frequency 50Hz three-phase power system, as a protection and control appliances, due to the special advantages of the vacuum circuit breaker, especially suitable for rated current frequency operation, or multiple open current places.

ZN63(VS1)-12C indoor AC vacuum circuit breaker adopts fixed installation, mainly used for fixed switchgear, the circuit breaker can be used alone, but also can be used for ring network power supply, box transformer or various non-standard power supply systems.

Packing

Download

Product Video

Play Video

Faq

  • 1. What are the advantages of ZN63A(VS1-12) Series Indoor Vacuum Circuit Breaker?

    The product has the advantages of compact and novel structure, reliable insulation, no pollution, no explosion risk, stable performance, high technical parameters, long maintenance cycle, complete operation functions and so on. The main part of the circuit breaker is arranged in the insulation cylinder made of epoxy resin cast by APG process. This structure can effectively prevent the influence of external factors including external force impact and dirty environment on the vacuum arc extinguishing chamber. And the main insulation cylinder with internal and external skirt, creepage ratio exceeds the national standard requirements, has a very high insulation performance, adapt to various harsh environments. The circuit breaker adopts the integrated design of the operating mechanism and the circuit breaker body, the front and back arrangement, the operating mechanism is specially optimized design, the transmission efficiency is high, the mechanical characteristics are stable, and the life span is more than 20,000 times. The circuit breaker can be used as a fixed installation unit, or a special propulsion mechanism to form a handcart unit, and can be flexibly matched with various domestic complete sets of equipment. It has become the absolute mainstream product of 12kV vacuum circuit breaker in China.

  • 2. How is it operated?

    It is equipped with a dedicated driving mechanism, allowing it to be used as a trolley unit for easy operation within switchgear.

  • 3. What safety features does it have?

    It includes a reliable interlocking unit to provide “five-prevention” protection functions, enhancing safety during operation.