Dropout Fuse Cutout is a kind of outdoor used high voltage protective device.To be connected with incoming feeder of distribution transformer or distribution line it mainly protect transformer or lines from short circuit and overload,and on/off loading current.

Product Description

Dropout Fuse Cutout is composed of insulator supports and fuse tube,static contacts is fixed on two sides of insulator support and moving contact is installed on two ends of fuse tube.Fuse tube is composed of inside extinguishing tube,outer phenolic compound paper tube or epoxy glass tube.Load switching fuse cutout provides enforced elastic auxiliary contacts and arc-extinguishing enclosure for switching on/off loading current.At normally working via fuse link tightened the fuse tube is fixed to form up of close position.In case system occur faults,fault current result in fuse melt immediately and take place electric arc,which let arc-extinguishing tube being heated and explode a lot of gas.This will produce high pressure and blow off the arc along with tube.

After fuse link melt moving contact has no tightened strength again,mechanism is locked and fuse tube dropout.Cutout now is in open position.

When it needs to switch off during cut out loading.Operator shall via insulating operating bar pull the moving contact,at its beginning main contact and auxiliary static contact is contacted still.

Whiling pulling the auxiliary contact is separated between auxiliary contacts there occur electric arc and the arc will be lengthened in arc-extinguishing enclosure gap and meanwhile arc-extinguishing explode gas to blow off the arc during current passing zero.

Material:Silicone rubber or Porcelain.
Manufacturing Standard:IEC 60282-2.

 

Parallel-groove connector

Tinned for No.6 soild through 250 KC mil stranded copper or aluminum.

Recoil bar

Heavy galvanized steel(which is also used for inserts, hangers, structural bolts and nuts)

Brid proof-design insulator

Higher insulation characteristics than ANSI distribution-cutout standards and equal in most cases to ANSI switch and bus standards

Lower contacts

Not visible-silver-to-silver, provide dual current path, independent of hingepivot, Stainless-steel backup springs prevent arcing when tube rises in hinge during recoil

Upper Contacts

Silver-to-siver at both surfaces

Attachment hooks

For load buster. Heavy construction also serves to guide tube during closing

Fuse tube

Fiber-lined epoxy fiber glass

Toggle joint

Collapses to permit dropout when link severs

Sturdy ferrules

Pinned to top and bottom of tube for permanent alignment, Large, accessible lifting ring.

Trunnion pocket

Secures tube in hinge during closing

Trunnion casting

Surfaces around trunnion bear on broad hinge surfaces to keep tube in alignment during closing

Flipper

Gives high-speed terminal separation, quick cable flip-out, and(in concoction with the toggle joint) reduces transmission of forces to fuse link during closing

Specifications

Technical Details

Type model Rated voltage

(kV)

Rated current

(A)

Breaking current

(kA)

Impulse

voltage BIL

(kV)

Power frequency

withstand voltage

(kV)

Leakage distance

(mm/kV)

Material
HRW-11/100 11 100 6.3 100 35 25-31 Polymer
HRW-11/200 11 200 10 100 35 25-31 Polymer
HRW-11/400 11 400 12.5 100 35 25-31 Polymer
HRW-12/100 12 100 6.3 110 40 25-31 Polymer
HRW-12/200 12 200 10 110 40 25-31 Polymer
HRW-15/100 15 100 6.3 125 45 25-31 Polymer
HRW-15/200 15 200 10 125 45 25-31 Polymer
HRW-18/100 18 100 6.3 130 50 25-31 Polymer
HRW-18/200 18 200 10 130 50 25-31 Polymer
HRW-21/100 21 100 6.3 140 58 25-31 Polymer
HRW-21/200 21 200 10 140 58 25-31 Polymer
HRW-24/100 24 100 6.3 150 65 25-31 Polymer
HRW-24/200 24 200 10 150 65 25-31 Polymer
HRW-27/100 27 100 6.3 160 68 25-31 Polymer
HRW-27/200 27 200 10 160 68 25-31 Polymer
HRW-30/100 30 100 6.3 170 70 25-31 Polymer
HRW-30/200 30 200 10 170 70 25-31 Polymer
HRW-33/100 33 100 6.3 175 75 25-31 Polymer
HRW-33/200 33 200 10 175 75 25-31 Polymer
HRW-33/400 33 400 12.5 175 75 25-31 Polymer
HRW-36/100 36 100 6.3 180 80 25-31 Polymer
HRW-36/200 36 200 10 180 80 25-31 Polymer

Product Advantages

  • 1. Lightweight and Easy to Handle: Polymer dropout fuse cutouts are significantly lighter than their porcelain counterparts, making them easier to handle, transport, and install. This reduces labor costs and installation time.
  • 2. High Strength and Durability: Made from high-strength polymer materials, these fuse cutouts offer excellent mechanical strength and durability.
  • 3. Superior Weather Resistance: Polymers used in dropout fuse cutouts are highly resistant to UV radiation, moisture, and temperature extremes.
  • 4. Improved Insulation Properties: Polymers provide excellent insulation properties, reducing the risk of electrical faults and improving the overall safety of the electrical system.
  • 5. Hydrophobic Surface: The hydrophobic nature of polymer materials ensures that water and other contaminants do not adhere to the surface. This helps in maintaining the insulating properties and reducing the risk of flashovers and electrical faults, even in wet or polluted environments.
Polymer Dropout Fuse Cutout

Application Places

Polymer Dropout Fuse Cutouts are used in various applications within the power transmission and distribution industry. Here are the main application places:

1. Overhead Distribution Lines: Polymer Dropout Fuse Cutouts are widely used in overhead power lines to protect transformers, capacitor banks, and branch lines from faults and overloads.

2. Transformers: These fuse cutouts are installed on distribution transformers to provide overcurrent protection and to isolate the transformer in case of a fault.

3. Capacitor Banks: They are used to protect capacitor banks in distribution networks by disconnecting them during fault conditions.

4. Branch Circuits: Fuse cutouts are employed on branch circuits to protect the equipment and cables from damage due to overcurrents or faults.

5. Renewable Energy Installations: They are increasingly used in renewable energy systems, such as solar and wind farms, to protect the equipment and ensure safe operation.

6. Industrial and Commercial Facilities: Polymer Dropout Fuse Cutouts are also utilized in industrial and commercial facilities for protecting various electrical equipment and ensuring reliable power supply.

These applications highlight the importance of Polymer Dropout Fuse Cutouts in maintaining the safety and reliability of electrical distribution systems.

Packing

Download

Product Video

Play Video

Faq

  • 1.What is a Polymer Dropout Fuse Cutout?

    A Polymer Dropout Fuse Cutout is a protective device used in electrical distribution systems to safeguard transformers, capacitor banks, and other equipment from overcurrent conditions and faults. It consists of a polymer housing that encases a fuse element.

  • 2.What are the advantages of using polymer materials in fuse cutouts?

    Polymer materials offer several benefits including high mechanical strength, excellent electrical insulation properties, resistance to UV radiation, and lightweight construction. They also provide better resistance to environmental factors such as moisture and pollution compared to traditional porcelain.

  • 3.How does a Polymer Dropout Fuse Cutout work?

    When an overcurrent or fault occurs, the fuse element inside the cutout melts, causing the fuse to drop out and create an open circuit. This action isolates the faulty section of the network, preventing damage to other equipment and ensuring safety.

  • 4.Where are Polymer Dropout Fuse Cutouts typically installed?

    They are typically installed on overhead distribution lines, distribution transformers, capacitor banks, branch circuits, renewable energy installations, and in industrial and commercial facilities.

  • 5.How do you select the appropriate fuse rating for a Polymer Dropout Fuse Cutout?

    The fuse rating is selected based on the load current and the maximum fault current the system can experience. It’s important to consider the protection requirements of the specific equipment being safeguarded and to consult manufacturer guidelines and standards for proper selection.

  • 6.What maintenance is required for Polymer Dropout Fuse Cutouts?

    Regular visual inspections are recommended to check for signs of damage, contamination, or wear. Additionally, periodic testing and cleaning may be necessary to ensure optimal performance. It’s important to follow the manufacturer’s maintenance guidelines.

  • 7.Can Polymer Dropout Fuse Cutouts be used in high pollution areas?

    Yes, polymer cutouts are particularly well-suited for high pollution areas due to their superior resistance to contaminants and UV radiation. Their hydrophobic properties help in maintaining insulation performance in polluted environments.

  • 8.Are Polymer Dropout Fuse Cutouts compatible with existing electrical systems?

    Yes, Polymer Dropout Fuse Cutouts are designed to be compatible with existing electrical systems and can often be used as direct replacements for older porcelain fuse cutouts, providing improved performance and reliability.