The (H)GW series outdoor Air/Load breaker switch is a three-phase AC 50Hz /60Hz outdoor medium-voltage switchgear, which can open and close the power line and can see the obvious disconnect distance.

Product Description

1. General

The (H)GW series outdoor Air/Load breaker switch is a three-phase AC 50Hz /60Hz outdoor medium-voltage switchgear, which can open and close the power line and can see the obvious disconnect distance.

Application voltage levels include 12kV, 24kV and 36kV

Application standard:lEC62271-102

2.Service and Installation Conditions

2.1. height above sea level: ≤3000m
2.2. Air temperature:-40℃~+50℃
2.3. Relative humidity: Daily mean 95%
monthly average 90%
2.4.Maximum wind speed: s34m/ s
2.5.Earthquake intensity: <8 degree
2.6.lcing thickness:<10mm
2.7.Thickness of snow:<35mm
2.8.lrradiance:<0.1W/cm2
2.9.Pollution grade:Ⅲ class、IVclass
2.10. Installation site: No fire disaster, explosion danger, chemical corrosion and frequent strenuous vibration places

Specifications

Pole-mounted Air Breaker Switch

  1. Technical parameters

 

Item Unit Data
Rated voltage kV 12 24 36
Rated frequency Hz 50/60
Rated current A 400 / 630
Rated short-circuit withstand/breaking current kA 12.5
Rated short-circuit making current (peak) kA 31.5
Rated peak withstand current kA 31.5
Rated short-circuit time Sec 1
Mechanical Operations Times 5000
Power frequency withstand voltage (1 min) kV 28/32 50/60 70/80
Lightning impulse withstand voltage (peak) kV 76/85 125/145 170/190

 

Pole-mounted Load Breaker Switch

      2.Technical parameters

ltem Unit Data
Rated voltage kV 12 24 36
Rated frequency Hz 50/60
Ratedcurrent A 200/400/630
Rated short circuit withstand current(IS) kA 20
Rated peak withstand current(IS) kA 50
Rated making current kA 31.5-50
Rated insulation leve(HV) Lightning impulse kA 75/85 125/145 170/195
Power frequency withstand 45 55/75 75/100
Rated short circuit breaking capacity cos.中(0.7) Without maintenance of contacts
For active circuits 20breakings 630 630 400
30breakings A 400 400 300
40breakings 300 300 250
50breakings 250 250 170
75breakings 170 170 160
120breakings 110 110 110
200breakings 65 65 65
280breakings 50 50 50
For ring circuits A 630 400 250
Rated breaking capacity of transformer A 50
Rated breaking capacity of cable charging A 11
Rated breaking capacity of earthing fault A 56

Note: The LBs type on load break switch (Switch disconnector) is equipped with stored energy released by fuse strike pins. The stored energy mechanism for the opening oparation is relaased by fuse strike pins.

The trip actuator is mounted on top of the fuse contact clip.

The DIN ivpe fuse is held in soring tvpe conlacts, secured by a tail lever, All the components are made of stainless steel, to preventcorrosion, have Jong live, and in the reset position. The trip lever is parked in an over-centre position.

 

 

 

Product Advantages

  • 1.Compact design
  • 2.All steel parts either in stainless steel or hot-dip galvanized
  • 3.Solid and stable base frame
  • 4.Main contact with icing protection
  • 5.Insulators available in porcelain or alternatively in silico ne
  • 6.Minimal sag for the line-connection thanks to the two fixed terminals
  • 7.Completely maintenance antirust AL alloy -Arc chamber
  • 8.Switching-off procedure without external arc
  • 9.Short circuit making capacity under specific conditions possible
  • 10.Fixing on the supporting structure either by clamping (free setting) or screwing (holes in the base frame)
  • 11.Easy on-site installation and setting
  • 12.High reliability: up to 1 ‘000 cycles (depending on the making current)

Application Places

Pole-mounted Air/Load breaker switch is a special switch, it is mainly used in the Pole to ensure the safety of a class of safety switch, generally speaking, the column switch is installed on the pole, its main role is used to isolate the high voltage circuit, is a typical outdoor isolation switch.

Packing

Download

Product Video

Play Video

Faq

  • What are the applications of Pole-mounted Air/Load breaker switch?

    1. Switching of the distribution system: the pole-mounted switch can be used to switch different power supplies.

    2. Load distribution: the pole-mounted switch can be used to distribute the power load to different circuits to ensure the load balance between each circuit and avoid overload.

    3. Fault isolation of the distribution network: When the distribution network fails, the pole-mounted switch can quickly cut off the fault circuit to avoid the expansion of the fault.

    4.Maintenance and overhaul: the pole-mounted switch can also be used for maintenance and overhaul work

    5. Remote control of the power system: In modern power systems, the pole-mounted switch can be connected with the monitoring system to achieve remote control to improve the flexibility and efficiency of the operation.