| Item | Unit | Specification | |
| Rated voltage | kV | 126 / 145 | |
| Rated insulating level | Lightning impulse withstand voltage (1.2/50 μs) | kV | 650 / 550 |
| Power frequency withstand voltage (1min) | kV | 300 / 230 | |
| Rated current | A | 2500/3150 / 4000 | |
| Rated short circuit withstand/breaking current | kA | 31.5 / 40 / 50 | |
| Maximum short-circuit current | kA | 80 (1000 / 125) | |
| Making current | kA | 82 / 1000 / 125 | |
| Out-of-phase breaking current | kA | 8 / 10 / 125 | |
| Rated SF6 pressure (20°C REL) | MPa | 0.40 / 0.50 | |
| Lockout pressure (20°C REL) | MPa | 0.30 / 0.40 | |
| Breaking times of the rated short circuit withstand/breaking current | Times | 20 | |
| Mechanical life | Times | 1000 | |
| Closing time (under rated operating voltage) | S | 0.06 | |
| Rated operating sequence | O-0.3s-CO-180s-CO | ||
| Switching single capacitor bank current | A | 400 | |
| Rated short-circuit duration | S | 4 | |
| Annual leakage | %Year | ≤0.3 | |
| Moisture content of SF6 (20°C) | uL/L | ≤150 | |
| Voltage of stepping and charging | V | AC: 220 / 380 DC: 48 / 110 / 220 | |
| Voltage of charging motor | V | AC: 220 DC: 110 / 220 | |


It utilizes advanced SF6 gas technology that offers outstanding dielectric strength and arc-quenching capabilities, ensuring safe operation under high voltage conditions.
Yes, with its robust and compact design, it is ideal for installations where space is limited, such as urban areas, as well as for applications in tough outdoor environments.
Due to its advanced safety mechanisms and robust construction, the circuit breaker offers high reliability and a long service life.