| Item | Unit | Specification | |
| Rated voltage | kv | 72.5 | |
| Rated insulating level | Lightning impulse withstand voltage (1.2/50 μs) | kv | 410 / 350 |
| Power frequency withstand voltage (1min) | kv | 200 / 160 | |
| Rated current | A | 2000 / 2500 / 3150 / 4000 | |
| Rated short circuit withstand/breaking current | kA | 31.5 / 40 / 50 | |
| Rated short-circuit making current | kA | 80 / 1000 / 125 | |
| Rated short circuit switching current | kA | 80 / 1000 / 125 | |
| Rated out-of-phase breaking current | kA | 8 / 10 / 12.5 | |
| Rated SF6 pressure (20°C REL.) | MPa | 0.40 / 0.50 | |
| Lockout pressure (20°C REL.) | MPa | 0.30 / 0.40 | |
| Breaking times of the rated short circuit withstand/breaking current | Times | 20 | |
| Mechanical life | Times | 10000 | |
| Closing time (under rated operation voltage) | S | ≤0.1 | |
| Opening time (under rated operation voltage) | S | ≤0.06 | |
| Rated operating sequence | O-0.3s-CO-180s-CO | ||
| Rated switching single capacitor bank current | A | 400 | |
| Rated short-circuit duration | S | 4 | |
| Annual leakage | %Year | ≤0.3 | |
| Moisture content of SF6 (20°C) | uL/L | ≤150 | |
| Voltage of opening and closing coil | V | AC: 220 / 380 DC: 48 / 110 / 220 | |
| Voltage of charging motor | V | AC: 220 DC: 110 / 220 | |
1. Superior Safety Features: The LW36-126(145) Series Circuit Breaker is equipped with advanced SF6 gas technology, which guarantees exceptional dielectric strength and superior arc-quenching performance, ensuring the highest levels of safety in high-voltage electrical systems.


It is recommended to check the SF6 gas level and pressure annually or according to the manufacturer’s guidelines to ensure optimal performance and safety.
Operators should be trained in high-voltage safety procedures and familiar with the specific operation and maintenance manual of the LW36-126(145) Series Circuit Breaker.
Safety precautions include ensuring the circuit is de-energized before maintenance, using appropriate personal protective equipment (PPE), and following lockout/tagout procedures.