| Item | Unit | Specification | ||||
| Rated Voltage | kV | 36 | 72.5 | 123 | 145 | |
| Rated Current | A | 630, 1250, 1600, 2000, 2500, 3150 | ||||
| Rated short withstand current and time | kA/s | 25~50 / 4 | ||||
| Rated perk/marking withstand current | kA | 63~125 | ||||
| Lightning impulse withstand voltage (1.2/50 μs) | To earth | kV | 200 | 325 | 500 | 650 |
| To phase | kV | 200 | 325 | 500 | 650 | |
| Across open DS | kV | 215 | 405 | 650 | 750 | |
| 1min power frequency withstand voltage | To earth | kV | 95 | 140 | 230 | 275 |
| To phase | kV | 95 | 140 | 230 | 275 | |
| Across open DS | kV | 118 | 180 | 300 | 315 | |
| Rated mechanical terminal load | Level of lateral load | N | 750 | 750 | 1500 | 1500 |
| Level of vertical load | N | 500 | 500 | 1000 | 1000 | |
| Vertical force | N | 750 | 750 | 1000 | 1000 | |
| Max. Manual operating moment | N.m | 200 | ||||
| Control voltage | V | AC 220, DC 110/220 | ||||
| Motor voltage | V | AC 220/380, DC 110/220 | ||||


The GW5 Series Disconnector consists of two rod-type post insulator porcelain bottles arranged in a 50° V-shape structure fixed on the base, mainly including the base, rod-type post insulator porcelain bottles, connection seat assembly, left and right contact head assembly, and grounding knife assembly.
Servicing requires wearing appropriate personal protective equipment, checking grounding conditions, ensuring warning signs are hung on the operation handles, and ensuring the power supply to the electric operating mechanism is disconnected.
The GW5 Series Disconnector offers flexible installation methods, including horizontal installation, angled installation, and various special installation methods.