The cutout bases and fuse carriers shall have the following current ratings at 230/400V:Three phase and neutral for transformers up to 500kVA:400A; and Three phase and neutral for transformers above 500kVA: 630A.
The outer housing of the units shall be comprised of Grey insulating material of sufficient mechanical strength as to prevent it from becoming damaged. The material shall be resistant to ultra violet degradation and have flame retardant properties. The Grey colour shallbe RAL 7035 code system according to DNA(German Standards Board.Frankfurt.Germany)
The fuse carrier shall be required to take J.P. type cartridge fuse links with 82mm centers, conforming to BS 88. Tightening screws shall have insulated tops to enable the fuse carrier to be removed without safety devices(rubber gloves, etc.)
| Item | JHU | JPU | JSU |
|---|---|---|---|
| Rated voltage | 415/500V AC | 415/500V AC | 415/500V AC |
| Rated breaking capacity | 50kV | 50kV | 50kV |
| Standard | IEC 60269-2-1 BS 88-2 | IEC 60269-2-1 BS 88-2 | IEC 60269-2-1 BS 88-2 |
| Rated current | Gg/Q1 | Gg/Q1 | Gg/Q1 |
| Rated current | 20A-800A | 20A-800A | 20A-800A |
The FUSE CARRIER is used in various electrical distribution scenarios to protect equipment and maintain system reliability. Some common usage scenarios include:


1. Operate in strict accordance with the closing sequence to avoid electrical damage or safety accidents caused by improper operation;
2. The external connection cable should be fixed firmly to prevent accidents such as poor contact;
3. The fuse should be replaced in time to ensure the normal operation of the electrical equipment;
4. Keep the equipment clean and dry, and avoid using the electrical equipment in a humid environment.