FLN36-12D type indoor use high voltage AC load break switch is developed by our company and absorbing international latest technology and according to our domestic standards, completely comply with lEC420,1EC694, lEC129 and national standard: GB3804 “3.6~40.5KV high voltage AC load break switch”,GB1985-2004 “High voltage AC disconnector and earth switch”GB/T11022-1999 “High voltage switchgear and controlgear: General technical requirements” , it is main switch for ring main unit.

Product Description

Product Overview:

The FLN36-12D/FLRN36-12D indoor AC high voltage sulfur hexafluoride load switch is a cutting-edge product developed by our company to meet the operational requirements specific to our country. This advanced load switch has undergone comprehensive type testing and adheres to the standards of GB3804 (363kV AC High Voltage Load Switch), GB1926 (High Voltage Load Switch Fuse Combination Electrical Appliances), IEC60265, and IEC60420. Designed to ensure high performance and reliability, it is an essential component for modern urban power grids.

Structural Features:

  1. Three-Station Extinguishing Chamber:
    • Provides “closing, opening, and grounding” functions, ensuring reliable operation and safety.
  2. Reliable Interlocking:
    • Features reliable interlocking mechanisms to prevent incorrect operations, enhancing safety.
  3. High Insulation Strength:
    • The fracture has high insulation strength with a large creepage distance design, ensuring safe and stable operation.
  4. Voltage Equalizing Protection Cover:
    • Equipped with a voltage equalizing protection cover at the outlet end to ensure balanced voltage distribution.
  5. Electric Turn-On Load Switch:
    • Comes with an electric turn-on load switch for ease of operation.
  6. Touchable Electric Braided Front Connector:
    • The outlet end is equipped with a touchable electric braided front connector for secure and reliable connections.
  7. High-Voltage Cables:
    • Both inlet and outlet lines are equipped with high-voltage cables, suitable for use in cable branch (junction) boxes.
  8. Special Sealing Design:
    • Features a special dynamic and fixed sealing design to ensure reliable sealing and longevity.
  9. Pressure Gauge:
    • A prominently positioned pressure gauge is included for monitoring during operation, ensuring safe and reliable operation.

Installation Method:

  1. Site Preparation:
    • Ensure the installation site is clean, dry, and free from dust and other contaminants.
  2. Mounting:
    • Securely mount the load switch on a stable and rigid surface within the indoor electrical distribution panel or switchgear unit using the provided brackets and hardware.
  3. Electrical Connections:
    • Connect the high-voltage cables to the inlet and outlet terminals, ensuring tight and secure connections. Follow the provided wiring diagram for correct installation.
  4. Grounding:
    • Properly ground the switch to prevent electrical hazards by connecting the grounding terminal to the panel or switchgear’s grounding busbar.
  5. Testing:
    • Perform insulation resistance and continuity tests to verify correct installation. Test the operation of the switch by opening and closing it several times to ensure functionality.

Applicable Environmental Conditions:

  1. Temperature Range:
    • Suitable for operation in temperatures ranging from -25°C to +40°C, ensuring reliable performance in typical indoor environments.
  2. Humidity:
    • Designed to operate effectively in environments with relative humidity up to 90%, providing reliability in various indoor conditions.
  3. Altitude:
    • Capable of operating at altitudes up to 1000 meters without derating, making it suitable for a wide range of installations.
  4. Pollution Degree:
    • Suitable for environments with a pollution degree of up to PD3, ensuring safe operation in moderately polluted environments.

Model and meaning

Specifications

No. Description Unit  Specitications

 

1  Rated voltage KV 12
2 Rated Frequoncy Hz 50
3 Rated current A 630
4  Rated peak withstand current kA 50
5  Rated short time withstand current 4s kA 20
6  Rated short circuit making current (peak) kA 50
7  Rated breaking current

 

 

 Active load breaking current A 630
 Closed loop breaking current A 630
 Cable charging breaking current A 10
8 Rated power trequency withstand voltage(1min)
To earth and between phases/Across the isofating distances
kv 42/48
9 Rated lighting impulse withstand voitage(peak)
To earth and between phases/Across the isolating distances
kv 75/85
10 Rated SF6 gas pressure (abs20℃) Mpa ≤0.04
11 Rated operating voltage (electric) v AC220DC220

 

12  Rated voltage of shunt release v AC220、DC220

 

13  Average opening speed m/s 3.5±1.5
14 Average closing speed m/s 3.5±1.5
15  Opening and closing the same period of the three-phase ms 53
16 Main circuit resistance μ Ω ≤120
17  Maximum torque manual operation N.m ≤160
18  Between phases center distance mm 210±0.5

Product Advantages

  • 1. Advanced Contact Structure: The load switch features a double break, rotary moving contact structure, offering three distinct operating states: closed, open, and grounded.
  • 2. SF6 Gas Insulation: Utilizes SF6 gas as the extinguishing and insulating medium. The main circuit is sealed within upper and lower shells cast from epoxy resin, ensuring that electrical conductivity remains unaffected by external environmental conditions.
  • 3. Enhanced Safety Performance: Designed with internal arc safety in mind, the switch has a structural weak point that will blow open in case of an internal arc. This action triggers the arc relief valve above the cabinet to guide overpressure airflow outside, ensuring the safety of the switch cabinet during inspections.
  • 4. Integrated Design: The load switch integrates the closing, opening, and grounding functions into one compact unit. Encased in an SF6 gas-filled epoxy resin shell, it features interlocking mechanisms for the three positions, ensuring high safety and reliability.
  • 5. Compact and Maintenance-Free: With its small size, light weight, and maintenance-free design, the load switch is easy to operate and safe to use, providing a user-friendly experience while maintaining high performance and reliability.
FLN36-12D indoor AC high-voltage load switch

Application Places

  • Urban Power Grid Construction:
  • Used in the construction and renovation of urban power grids.
  • Provides reliable switching for load currents and fault currents in city networks.
  • Industrial and Mining Enterprises:
  • Ideal for industrial applications where high-voltage switching is required.
  • Ensures safe and efficient power distribution in mining operations.
  • High-Rise Buildings:
  • Utilized in the electrical systems of high-rise buildings.
  • Manages power distribution and provides protection against electrical faults.
  • Residential Areas:
  • Employed in residential electrical systems for reliable power supply.
  • Pre-Installed Substations:
  • Suitable for use in pre-installed substations for power distribution.
  • Facilitates the control and protection of power lines and transformers.

 

 

Packing

Download

Product Video

Play Video

Faq

  • 1. What switch is FLN36-12D?

    FLN36-12D is an indoor high-voltage SF6 load switch, suitable for indoor switchgear with a rated voltage of 12KV. The switch adopts SF6 gas as the extinguishing and insulating medium, and has the characteristics of small volume, easy installation and use, and strong adaptability to the environment. The main circuit and ground circuit of the FLN36-12D load switch are sealed in an insulating shell made of epoxy resin cast by APG process. This design not only has excellent insulation properties, but also can resist the influence of dirty environment. In addition, the insulation shell is combined with the upper and lower insulation covers, and the inside is filled with SF6 gas with a relative pressure of 0.1bar. The lower insulation cover has protective measures to ensure that the overpressurized SF6 gas is directly sprayed into the rear channel of the cabinet in case of an accident, so as to ensure personal safety.

  • 2. What are the main features of the FLN36-12D load switch?

    • It has a double-fracture and rotary contact structure with three operational statuses: on, off, and ground connection.
    • It uses SF6 gas as an arc-extinguishing and insulating medium, ensuring high reliability and safety.
    • The main circuit is sealed within an epoxy shell, protecting it from external environmental influences.
    • It has a good safety performance with a design that directs gas out of the cabinet in case of internal arcing, ensuring the safety of the equipment.
  • 3. What are the environmental conditions for the FLN36-12D load switch?

    • The load switch is designed to operate in air temperatures ranging from -35°C to +40°C.
    • It can be installed at altitudes up to 2500 meters above sea level.